Functions of the basic unit (cat. no. 825-m…), Thermal overload – Rockwell Automation 825 Smart Motor Manager User Manual User Manual

Page 49

Advertising
background image

Functions 3-16

Publication 825-UM001B-EN-P January 2001

Table 3.I Control Functions Summary (Continued)

➊ For example, when used with two-speed motors

Functions of the Basic Unit (Cat. No. 825-M…)

Thermal Overload

The Smart Motor Manager accurately simulates thermal conditions in the motor for all
operating modes. This permits maximum utilization of an installation and assures safe
protection of the motor.
The basic unit uses a two-body simulation to calculate a more precise representation of a
motor’s thermal condition during all modes of operation. A two-body simulation incorporates
the temperature rise characteristics of both the stator windings and the iron mass of the
motor into the thermal image.
The simulation of the Smart Motor Manager accurately represents the conditions in the
motor at all times.

Functions

Factory

Setting

Setting

Range

Factory

Setting

Tripping

Delay

Range

Factory

Setting

Relays

Selection

Factory

Setting

Bulletin 825-MST Option Card, Control Input #2: (24V AC/DC; 8 mA)

One of three functions can be selected:
1) Pickup delay, relay

#3

Off

0…240 s

1 s

#3

1) Dropout delay, relay

#3

0…240 s

2 s

#3

2) Set second rated

current ➊

Off

0.5…

2 000 A

20 A

3) Disable protective functions:

Asymmetry/phase
failure

Off

High overload/jam

Off

Earth (ground) fault

Off

Short-circuit

Off

Underload

Off

Limiting starts/hour

Off

PTC

Off

PT100 (RTD)

Off

Bulletin 825-MLV Option Card

Star-delta starting

Off

Y-

at 1.1

,

e

Y-

at 1…240 s

10 s

Y: #4/

∆:#5