Table 3.h, Warning functions summary – Rockwell Automation 825 Smart Motor Manager User Manual User Manual

Page 47

Advertising
background image

Functions 3-14

Publication 825-UM001B-EN-P January 2001

Table 3.H Warning Functions Summary

➊ Only one relay per function can be selected: MR = main relay, AL = alarm relay, auxiliary relay #1…#5 (if

auxiliary relays #2 and #3 are assigned to the communication [refer to page

5-16

] they cannot be selected

here).

➋ Same setting as for the Underload Trip function.

Functions

Factory

Setting

Setting

Range

Factory

Setting

Tripping

Delay

Range

Factory

Setting

Relays

Selection

Factory

Setting

Bulletin 825-M… Basic Unit

Thermal utilization
(%

∆ϑ

load)

Off

50…99%

75%

AL, #1…5

AL

Asymmetry (%

,

e

)

Off

5…80%

20%

AL, #1…5

AL

High overloading (x

,

e

)

Off

1…6

,

e

2

,

e

AL, #1…5

AL

Underload

Off

25…100%➋

75%➋

AL, #1…5

AL

Bulletin 825-MST Option Card

Earth (ground) fault
(core balance c.t.)

Off

5 mA…50 A

500 mA

AL, #1…5

AL

Bulletin 825-MMV Option Card

PT100 input #1…#6 (RTD)
(stator, bearings)

Off

50…200

°

C

50

°

C

AL, #1…3

AL