Table 3.h, Warning functions summary – Rockwell Automation 825 Smart Motor Manager User Manual User Manual
Page 47

Functions 3-14
Publication 825-UM001B-EN-P January 2001
Table 3.H Warning Functions Summary
➊ Only one relay per function can be selected: MR = main relay, AL = alarm relay, auxiliary relay #1…#5 (if
auxiliary relays #2 and #3 are assigned to the communication [refer to page
] they cannot be selected
here).
➋ Same setting as for the Underload Trip function.
Functions
Factory
Setting
Setting
Range
Factory
Setting
Tripping
Delay
Range
Factory
Setting
Relays ➊
Selection
Factory
Setting
Bulletin 825-M… Basic Unit
Thermal utilization
(%
∆ϑ
load)
Off
50…99%
75%
—
—
AL, #1…5
AL
Asymmetry (%
,
e
)
Off
5…80%
20%
—
—
AL, #1…5
AL
High overloading (x
,
e
)
Off
1…6
,
e
2
,
e
—
—
AL, #1…5
AL
Underload
Off
25…100%➋
75%➋
—
—
AL, #1…5
AL
Bulletin 825-MST Option Card
Earth (ground) fault
(core balance c.t.)
Off
5 mA…50 A
500 mA
—
—
AL, #1…5
AL
Bulletin 825-MMV Option Card
PT100 input #1…#6 (RTD)
(stator, bearings)
Off
50…200
°
C
50
°
C
—
—
AL, #1…3
AL