Rockwell Automation 825 Smart Motor Manager User Manual User Manual
Page 112

5-9 Setting the Operational Parameters
Publication 825-UM001B-EN-P January 2001
Table 5.D Cat. No. 825-M… Operating Parameters (Continued)
➊ If Warm Starting is set to “off”, the programming menu skips to parameter Start Inhibit.
➋ If Start Inhibit is set to “off”, the programming menu skips to parameter Start Control.
➌ If Start Control is set to “off”, the programming menu skips to parameter Main Relay.
Group
Required
Option Card
Cat. No.
LCD
Setting
Range
Description
Warm start
—
On/Off ➊
Warm start
On/Off
—
4…60
Warm start possible every
___min.
—
50…100
Warm start tripping time as
a percentage of tripping
time from cold
Limiting number of
starts per hour
—
On/Off ➋
Limiting number of
starts/hour
On/Off
—
1…10
Maximum starts/hour
—
All relays
Maximum number of
starts/hour reached
Assignment of output relay
Monitoring startup
time
—
On/Off ➌
Monitoring starting time
On/Off
—
1…240
Maximum starting time
—
All relays
Starting time exceeded
Assignment of output relay
WARM STARTING
OFF
WARM START EACH
60 min
WARM TRIP TIME
70 %
START INHIBIT
OFF
MAX START/HOUR
2
START INHIB TRIP
MAIN RELAY
START CONTROL
OFF
START TIME
10 sec
START CONT TRIP
MAIN RELAY