5-9 Setting the Operational Parameters

Publication 825-UM001B-EN-P January 2001

Table 5.D Cat. No. 825-M… Operating Parameters (Continued)

➊ If Warm Starting is set to “off”, the programming menu skips to parameter Start Inhibit.
➋ If Start Inhibit is set to “off”, the programming menu skips to parameter Start Control.
➌ If Start Control is set to “off”, the programming menu skips to parameter Main Relay.

Group

Required

Option Card

Cat. No.

LCD

Setting

Range

Description

Warm start

On/Off ➊

Warm start
On/Off

4…60

Warm start possible every
___min.

50…100

Warm start tripping time as
a percentage of tripping
time from cold

Limiting number of
starts per hour

On/Off ➋

Limiting number of
starts/hour
On/Off

1…10

Maximum starts/hour

All relays

Maximum number of
starts/hour reached
Assignment of output relay

Monitoring startup
time

On/Off ➌

Monitoring starting time
On/Off

1…240

Maximum starting time

All relays

Starting time exceeded
Assignment of output relay

WARM STARTING
OFF

WARM START EACH
60 min

WARM TRIP TIME
70 %

START INHIBIT
OFF

MAX START/HOUR
2

START INHIB TRIP
MAIN RELAY

START CONTROL
OFF

START TIME
10 sec

START CONT TRIP
MAIN RELAY