9-11 Applications/Wiring
Publication 825-UM001B-EN-P January 2001
Motors with Low Idling Current (< 20%
,
e
)
Main Circuit
Figure 9.12 Application with Low Idling Current
If motors have an operational idling current of less than 20% I
e
, then the information “motor
switched on” must be fed with an auxiliary contact of the contactor into control input #1.
Settings
Display
•
Motor switched on
•
Motor current < 20%
,
e
825-MCM
825-M
1
3
5
2
4
6
L1
L2
L3
M
3~
24 V AC/DC
+
N
L
R
220...230V AC/DC: R = 27k
Ω
/ 5W
110...120V AC/DC: R = 12k
Ω
/ 4W
Y31
825-MST
Y32
–
CONTROL INPUT #1
ON
I MOTOR < 20 % IE
SPEED SWITCH
ON