9-11 Applications/Wiring

Publication 825-UM001B-EN-P January 2001

Motors with Low Idling Current (< 20%

,

e

)

Main Circuit

Figure 9.12 Application with Low Idling Current

If motors have an operational idling current of less than 20% I

e

, then the information “motor

switched on” must be fed with an auxiliary contact of the contactor into control input #1.

Settings

Display

Motor switched on

Motor current < 20%

,

e

825-MCM

825-M

1

3

5

2

4

6

L1

L2

L3

M

3~

24 V AC/DC

+

N

L

R

220...230V AC/DC: R = 27k

/ 5W

110...120V AC/DC: R = 12k

/ 4W

Y31

825-MST

Y32

CONTROL INPUT #1
ON

I MOTOR < 20 % IE

SPEED SWITCH
ON