Switching to a second rated current, Functions of the cat. no. 825-mlv option card, Phase sequence – Rockwell Automation 825 Smart Motor Manager User Manual User Manual

Page 86

Advertising
background image

3-53 Functions

Publication 825-UM001B-EN-P January 2001

The selected functions are completely disabled as long as the control input is “on”
(24V AC/DC).

No alarm

No trip, no reset

Tripping delays begin to run only after the function is re-enabled.

Switching to a Second Rated Current

In the Smart Motor Manager, a second value can be selected for the rated current I

e

. The

change to the second rated value is controlled by activating control input #2 with 24V
AC/DC.
Make sure the second rated current is compatible with the current range of the Cat.
No. 825-MCM current converter module.

Application

Two-speed motors

Briefly increased loading of the motor and installation

Maximum loading when the ambient temperature varies appreciably. Examples:
Exposed water pumps, different conveying capacities during, daytime and at night

Functions of the Cat. No. 825-MLV Option Card

Phase Sequence

Function

If a motor is switched on in the wrong direction of rotation, the installation can be adversely
affected. The Smart Motor Manager monitors the phase sequence when voltage is applied,
and prevents the motor starting in the wrong direction.

Applications

Mobile installations (e.g., refrigerated transporters, construction machines)

Installations that can be displaced as enclosed units (e.g., mobile crushers, conveyor
belts, saws)

If a reversed phase sequence must be expected after a repair.