Commissioning and Operation 6-4

Publication 825-UM001B-EN-P January 2001

Locked Rotor or Starting Current

Set the locked-rotor or starting current as the multiple of rated current I

A

: I

e

according to specifications given by the manufacturer.

If no specifications are available, the starting current can either be measured with the
current converter or read from Figure 6.1

The current converter factory setting is 6 x I

e

.

LCD:

Figure 6.1 Range of Starting Currents of Standard Motors Expressed as Multiple
of the Rated Service Current

P

N

1

Approximate value for 2-pole motors, speed 3 000 rpm

2

Approximate value for 4-pole motors, speed 1 500 rpm

3

Approximate value for 6-pole motors, speed 1 000 rpm

4

Approximate value for 8-pole motors, speed 750 rpm

P

N

Rated output power in service

Locked Rotor Time

Normal setting of locked rotor time (i.e., when using standard motors or permissible
locked rotor time is known)

The setting of the locked rotor time must be equal to or less than the value quoted by
the manufacturer.

The current converter factory setting is 10 s. If no application details are available and
the starting conditions are normal, leave the setting at 10 s.
LCD:

LOCKED ROT CURR
6.00 x Ie

2

0.4

1

2

0.2

4

10

20

40

100

200

3

4

6

8

10

1

1

2

3

4

I

e

I

A

kW

LOCKED ROT TIME
10 sec