7-6 Testing and Maintenance

Publication 825-UM001B-EN-P January 2001

Test with Single-Phase Current Source

The test with a 3-phase current source described on page

7-5

can also be performed with a

single-phase source. To do this, the earth (ground) fault protection by the Holmgreen method
must be switched off.

Figure 7.2 Test with a Single-Phase Current Source

ATTENTION

!

This test should be performed only by qualified personnel.

IMPORTANT

The test current may not flow through the core balance current
transformer.

825-MCM

825-M

1

3

5

2

4

6

A

M

3 ~

,

e

Connection

Connection

Advertising