Setting the Operational Parameters 5-8

Publication 825-UM001B-EN-P January 2001

Table 5.D Cat. No. 825-M… Operating Parameters (Continued)

➊ If Underload Trip is set to “off”, the programming menu skips to parameter UL Warning.
➋ If UL Warning is set to “off”, the programming menu skips to parameter Star Delta.
➌ If Star Delta is set to “off”, the programming menu skips to parameter Warm Starting.
➍ If Set Star Time is set to “off”, the programming menu skips to parameter Warm Starting.

Group

Required

Option Card

Cat. No.

LCD

Setting

Range

Description

Underload

On/Off ➊

Underload protection
On/Off

25…100

Underload trip
Tripping level…%

,

e

1…60

Underload trip
Tripping delay

All relays

Underload trip
Assignment of output relay

0…240

Underload trip
Start delay

On/Off ➋

Underload warning
On/Off

All except

main relay

Underload warning,
assignment of output relay
(warning level is equal to
tripping level, without
tripping delay)

Star-Delta
(Wye-Delta)
starting

825-MLV

On/Off ➌

Star-delta starting
On/Off

Relay#4

Star-delta starting
Assignment of star output
relay

Relay#5

Star-delta starting
Assignment of delta output
relay

On/Off ➍

Star-delta starting
Max. time on star on/off

1…240

Star-delta starting
Max. time on star

UNDERLOAD TRIP
OFF

UL TRIP LEVEL
75 % Ie

UL TRIP TIME
10 sec

UNDERLOAD TRIP
MAIN RELAY

UL START-DELAY
0 sec

UL WARNING
OFF

UL WARNING
ALARM RELAY

STAR DELTA
OFF

STAR AUX REL #4

DELTA AUX REL #5

SET STAR TIME
OFF

STAR TIME
10 sec