5-15 Setting the Operational Parameters

Publication 825-UM001B-EN-P January 2001

Table 5.D Cat. No. 825-M… Operating Parameters (Continued)

➊ If Tamb in Thermal Image is set to “off”, the programming menu skips to parameter Output 4…20 mA.
➋ Limiting winding temperatures of the three insulations classes: E = 120°C, B = 130°C, F = 155°C. When the

ambient temperature is taken into consideration, the insulation class needs to be programmed for correction
of the thermal model. Without using PT100 #7 as the ambient temperature input, the thermal model bases
the thermal calculation on an ambient temperature of 40°C.

Group

Required

Option Card

Cat. No.

LCD

Setting

Range

Description

PT 100 (RTD)
temperature sensor,
continued

825-MMV

On/Off

PT100 #3 warning
On/Off

50…200

PT100 #3
Warning temperature

On/Off

PT100 #4 warning
On/Off

50…200

PT100 #4
Warning temperature

On/Off

PT100 #5 warning
On/Off

50…200

PT100 #5
Warning temperature

On/Off

PT100 #6 warning
On/Off

50…200

PT100 #6
Warning temperature

AL,

#1…#3

PT100, #1…#6 warning
Assignment of output relay

On/Off ➊

PT100 #7, allowance for
ambient temperature in
thermal simulation

B, E, F

Insulation class of
winding ➋

Analog output

825-MST

Thermal utiliz

, Motor

PT100 max.

Using the analog output for:
thermal utilization,
motor current,
max. PT100 temperature

PT100 #3 WARNING
OFF

#3 WARNING TEMP
50 °C

PT100 #4 WARNING
OFF

#4 WARNING TEMP
50 °C

PT100 #5 WARNING
OFF

#5 WARNING TEMP
50 °C

PT100 #6 WARNING
OFF

#6 WARNING TEMP
50 °C

#1-6 WARNING
OFF

Tamb IN TH IMAGE
OFF

INSULATION CLASS
B

OUTPUT 4…20 mA
THERMAL