5-7 Setting the Operational Parameters

Publication 825-UM001B-EN-P January 2001

Table 5.D Cat. No. 825-M… Operating Parameters (Continued)

➊ If EF Core Trip is set to “off”, the programming menu skips to parameter EF C Warning.
➋ If EF C Warning is set to “off”, the programming menu skips to parameter Short Circ Trip.
➌ If Short Circ Trip is set to “off”, the programming menu skips to parameter Underload Trip.

Group

Required

Option Card

Cat. No.

LCD

Setting

Range

Description

Earth (ground) fault

825-MST

On/Off ➊

Earth (ground) fault
protection (core balance
transformer) On/Off

1…2 000

Core balance transformer
current ratio

5…999 mA

1.00…50.00 A

Earth (ground) fault trip
(core balance transformer)
Tripping level

0.1…5

Earth (ground) fault trip
(core balance transformer)
Tripping delay

All relays

Earth (ground) fault
warning (core balance
transformer)
Assignment of output
relay

On/Off ➋

Earth (ground) fault
warning (core balance
transformer) On/Off

5…999 mA

1.00…50.00 A

Earth (ground) fault
warning (core balance
transformer)
Tripping level

All except main

relay

Earth (ground) fault
warning (core balance
transformer)

Short circuit

825-MST

On/Off ➌

Short-circuit protection
On/Off (h.v. motors only)

4.0…12.0

Short-circuit trip
Tripping level…

,

e

20…990

Short-circuit trip
Tripping delay

Relay #1/

no relay

Short-circuit trip, choice
between output relay #1
and no relay

EF CORE TRIP
OFF

CORE C.T. RATIO
1

EF C TRIP LEVEL
1 A

EF C TRIP TIME
0.50 sec

EF CORE TRIP
MAIN RELAY

EF C WARNING
OFF

EF C WARN LEVEL
500 mA

EF C WARNING
ALARM RELAY

SHORT CIRC TRIP
OFF

SC TRIP LEVEL
10.00 x Ie

SC TRIP TIME
50 ms

SHORT CIRC TRIP
AUX RELAY #1