Main current transformers for the motor circuit, Table 2.g, Main current transformer ratings – Rockwell Automation 825 Smart Motor Manager User Manual User Manual

Page 30

Advertising
background image

2-10 Equipment Description

Publication 825-UM001B-EN-P January 2001

Main Current Transformers for the Motor Circuit

When the Cat. No. 825-M Control and Protection Unit is used as a secondary relay with Cat.
Nos. 825-MCM2 and 825-MCM20, the following specifications apply:

Table 2.G Main Current Transformer Ratings

➊ Designation according to IEC 60044 part 2:

With starting current 10

,

e

: class 5 P 20

The current transformer error in addition to the basic unit error

➋ 2.5 A with Cat. No. 825-MCM2, 20 A with Cat. No. 825-MCM20

Minimum nominal operating voltage

Nominal operating voltage of motor

Minimum rated primary current

,

1n

Nominal operating current of motor

Rated secondary current

1 A or 5 A

Class and nominal
overcurrent factor

5 P 10 ext. 120% ➊

Power rating

According to power consumption in leads

and measuring circuits

Rated frequency

50/60 Hz

Burden:

825-M +

825-MCM2

825-M +

825-MCM20

Power consumption at max. rated current

0.1 VA/phase

0.4 VA/phase

Continuous thermal current

3 A

24 A

Thermal current, 1 s duration

250 A

600A

Frequency of input current

50/60 Hz

50/60 Hz

General Notes on 825-MCM…

No-load

An open-circuit secondary is permitted, as the burden is

installed in the detection module

5

Total measurement error (percentage):
±5% within range up to rated nominal overcurrent (10X)
±1% at rated nominal primary current

P

For protection purposes

10

Rated nominal overcurrent factor: 10X rated nominal primary current

ext.
120%

Extended rated thermal current: 120% of rated nominal primary current (if

,

e

motor > 87% of

rated nominal transformer current)