Table 3.j, Thermal overload setting parameters – Rockwell Automation 825 Smart Motor Manager User Manual User Manual
Page 54

3-21 Functions
Publication 825-UM001B-EN-P January 2001
Table 3.J Thermal Overload Setting Parameters
➊ Up to 2 000 A, if primary current transformers are used.
➋ –5…60
°
C (23…140
°
F)
➌ UL/CSA 160…434 A
➍ The cooling factor can be modified to reflect different motor cooling with running motor and at standstill.
Detection Module ➋
825-MCM2
825-MCM20
825-MCM180
825-MCM630
825-MCM630N
Rated Current
Setting range
0.5…2.5 A ➊
2.5…20 A ➊
20…180 A
160…630 A ➌
160…630 A
Factory setting
20 A
20 A
20 A
20 A
20 A
Setting increments
0.01…2 A
0.1…2 A
1 A
2 A
2 A
Locked-Rotor Current (Multiple of Rated Current)
Setting range
2.5…12
,
e
Factory setting
6
,
e
Setting increments
0.1
,
e
Locked-Rotor Time (Admissible Locked-Rotor Time of Cold Motor)
Setting range
1…600 s
Factory setting
10 s
Setting increments
1 s
Cooling Factor of Motor Off/On ➍
Setting range
1…10
Factory setting
2.5
Setting increments
0.5
Resetting the Thermal Trip
Setting range
10…100% of thermal utilization
Factory setting
50%
Setting increments
1%
Ultimate Release Current
Incl. setting tolerance
1.05…1.15
,
e