Table 3.j, Thermal overload setting parameters – Rockwell Automation 825 Smart Motor Manager User Manual User Manual

Page 54

Advertising
background image

3-21 Functions

Publication 825-UM001B-EN-P January 2001

Table 3.J Thermal Overload Setting Parameters

➊ Up to 2 000 A, if primary current transformers are used.
➋ –5…60

°

C (23…140

°

F)

➌ UL/CSA 160…434 A
➍ The cooling factor can be modified to reflect different motor cooling with running motor and at standstill.

Detection Module

825-MCM2

825-MCM20

825-MCM180

825-MCM630

825-MCM630N

Rated Current

Setting range

0.5…2.5 A ➊

2.5…20 A ➊

20…180 A

160…630 A ➌

160…630 A

Factory setting

20 A

20 A

20 A

20 A

20 A

Setting increments

0.01…2 A

0.1…2 A

1 A

2 A

2 A

Locked-Rotor Current (Multiple of Rated Current)

Setting range

2.5…12

,

e

Factory setting

6

,

e

Setting increments

0.1

,

e

Locked-Rotor Time (Admissible Locked-Rotor Time of Cold Motor)

Setting range

1…600 s

Factory setting

10 s

Setting increments

1 s

Cooling Factor of Motor Off/On

Setting range

1…10

Factory setting

2.5

Setting increments

0.5

Resetting the Thermal Trip

Setting range

10…100% of thermal utilization

Factory setting

50%

Setting increments

1%

Ultimate Release Current

Incl. setting tolerance

1.05…1.15

,

e