Table 2.e, Relay ratings – Rockwell Automation 825 Smart Motor Manager User Manual User Manual
Page 28

2-8 Equipment Description
Publication 825-UM001B-EN-P January 2001
Table 2.E Relay Ratings
Contact Data of Output Relays
Main Relay (MR) 95…96
Contacts fitted
1 N/C and 1 N/O contact, galvanically separated
Nominal operating voltage
as per UL, CSA: pilot duty 240 V
[V]
24
110…125
220…250
380…440
Continuous thermal current
[A]
4
Rated operating current for AC-15
[A]
3
3
1.2
Max. permissible switching current
(cos
ϕ
= 0.3) AC-15
[A]
30
30
12
Rated operating current for DC-13
without prot. network,
L/R = 300 ms
[A]
2
0.3
0.2
–
Max. rated current of back-up fuse:
[A]
10 A, 500V AC, Type gG
Alarm Relay (AL), Auxiliary Relays #1, #4, #5
Contacts fitted
1 N/O contact each
Continuous thermal current
4 A
Max. permissible switching voltage
400V AC, 125 VDC
Nominal Operating Current
cos
ϕ
= 1
4 A at 250V AC or 30V DC
cos
ϕ
= 0.4, L/R = 7 ms
2 A at 250 VAC or 30V DC
Max. Switching Power
cos
ϕ
= 1
1 250 VA, 150 W
cos
ϕ
= 0.4, L/R = 7 ms
500 VA, 60 W
as per UL/CSA
240 V, 1 A pilot duty
Auxiliary Relays #2, #3
Contacts fitted
1 N/O contact each
Continuous thermal current
4 A
Max. permissible switching voltage
48 VAC, 30 VDC
Max. Switching Power
cos
ϕ
= 1
150 W
cos
ϕ
= 0.4, L/R = 7 ms
60 W