Checking the wiring, Switching on the control voltage, Checking the set parameters – Rockwell Automation 825 Smart Motor Manager User Manual User Manual

Page 121

Advertising
background image

Commissioning and Operation 6-2

Publication 825-UM001B-EN-P January 2001

Checking the Wiring

Primary current transformer, core balance current transformers

Converter module

Basic Unit

Link between basic unit and converter module

Inputs, outputs

Supply

Communication

Contacts 95…98 are marked according to “electrically held”/“non-fail-safe”
connection required.

Checking the Installation with the Control Voltage Applied

Switching on the Control Voltage

After applying control voltage, the current converter is ready for operation in
approximately 3 s.

LCD shows “ACTUAL VALUE”

Main relay; contact 95/96 is closed

Checking the Set Parameters

Methods

With the current converter in Set Values mode

Access the parameters (or print them out) and compare them with the set values in the list of
settings. The main settings are:

Rated or service current

Locked-rotor or starting current

Permissible locked-rotor time

These three settings must be made individually for each motor. Refer to page

5-4

, Operational

Parameters, for procedure.