Function summary, Table 3.g, Protective functions summary – Rockwell Automation 825 Smart Motor Manager User Manual User Manual

Page 46

Advertising
background image

3-13 Functions

Publication 825-UM001B-EN-P January 2001

Function Summary

Table 3.G Protective Functions Summary

➊ Via external speedometer (control input #1), output and trip relays as for high overload.
➋ Allowing for the ambient temperature in the thermal image.
➌ Only one relay per function can be selected: MR = main relay, AL = alarm relay, auxiliary relay #1…#5 (if

auxiliary relays #2 and #3 are assigned to the communication [refer to page

5-16

] they cannot be selected

here).

Functions

Factory

Setting

Setting

Range

Factory

Setting

Tripping

Delay

Range

Factory
Setting

Relays

Selection

Factory
Setting

Bulletin 825-M… Basic Unit

Thermal overload

On

100%

MR, No

MR

Asymmetry (phase failure)

On

5…80%

35%

1…25 s

2.5 s

All

MR

High overloading/jam

On

1…6

,

e

2.4

,

e

0.1…5 s

0.5 s

All

MR

Underload

Off

25…100%

75%

1…60 s

10 s

All

MR

Underload delayed enable

On

0…240 s

0 s

Earth (ground) fault (residual)

On

10…100%

50%

0.1…5 s

0.5 s

All

MR

Starting time monitor

Off

1…240 s

10 s

All

MR

Limited starts per hour

Off

1…10

2

All

MR

Bulletin 825-MST Option Card

Short-circuit

Off

4…12

,

e

10

,

e

20…990 ms

50 ms

#1, No

#1

Earth (ground) fault
(core balance c.t.)

Off

5 mA…50 A

1 A

0.1…5 s

0.5 s

All

MR

Stalling during start

Off

All ➊

MR ➊

Thermistor input (PTC)

Off

800 ms

All

MR

Bulletin 825-MLV Option Card

Phase sequence (motor supply)

Off

1 s

All

MR

Phase failure (motor supply)

Off

2 s

All

MR

Bulletin 825-MMV Option Card

PT100 input #1…#6 (RTD)
(stator, bearings)

Off

50…200

°

C

50

°

C

< 8 s

MR, AL

#1…#3

MR

PT100 input #7 (RTD) ➋

Off

ATTENTION

!

Warning function settings must be such that associated alarms are
actuated before a trip occurs.