Main circuit, Control circuit, Figure 9.3 – Rockwell Automation 825 Smart Motor Manager User Manual User Manual
Page 144: Basic unit and converter module, Figure 9.4, Control by momentary contact, Figure 9.3 basic unit and converter module, Figure 9.4 control by momentary contact, Basic unit settings

9-3 Applications/Wiring
Publication 825-UM001B-EN-P January 2001
Star-Delta Starter with Bulletin 825 Smart Motor Manager
Main Circuit
Figure 9.3 Basic Unit and Converter Module
Control Circuit
Figure 9.4 Control by Momentary Contact
825-MCM
825-M
L1 L2 L3
M
3~
1
3
5
2
4
6
1 3 5
2 4 6
1 3 5
2 4 6
A1
A2
K1H
A1
A2
K2D
A1
A2
K3Y
U1
F1
Ls
1)
U1 V1 W1
U2 V2 W2
Basic Unit settings:
FULL LOAD CURR
LOCKED ROT CURR
LOCKED ROT TIME
START TIME
FLC x 0.5774 [A]
,
BL
∆
(…x
,
e
)
W
BL
∆
(…sec.)
> t
startY
(…sec.)
U1 Converter module
Cat. No. 825-MCM2
Cat. No. 825-MCM20
Cat. No. 825-MCM180
Cat. No. 825-MCM630
Cat. No. 825-MCM630N
➊
➊ Core balance installation position
AL
A1
95
97
96
98
A2
A1
A2
(L2/F8)
N
H1
K1
H3
825-M
13
14
F7
L1
S0
S1
MR
F1
Us
A1
A2
53
63
54
64
825-MLV
F1
A1
A2
K3
K2
D
K1
H
H2
K1
Contactor
F1
Electronic control and protection
system Bulletin 825 with
Cat. No. 825-MLV option card
S1
On push button
S0
Off push button
U
s
Control voltage
H1
Indicator “Contactor closed“
H2
Indicator “825-M tripped“
MR Main relay
AL
Alarm relay
H3
Indicator “Alarm/Warning“