Phase failure (based on voltage measurement), Table 3.aa, Phase sequence setting parameters – Rockwell Automation 825 Smart Motor Manager User Manual User Manual

Page 87: Table 3.ab, Phase failure setting parameters

Advertising
background image

Functions 3-54

Publication 825-UM001B-EN-P January 2001

Table 3.AA Phase Sequence Setting Parameters

➊ If auxiliary relays #2 and #3 are assigned to the communication (refer to page

5-16

) they cannot be selected

here.

Phase Failure (Based on Voltage Measurement)

Function

A phase failure is recognized by measuring the voltages before the switchgear and thus with
the motor at standstill. (With phase failure protection where the phase currents are measured,
the motor first has to be switched on, although it cannot start with only two phases.)

Table 3.AB Phase Failure Setting Parameters

➊ If auxiliary relays #2 and #3 are assigned to the communication (refer to page

5-16

) they cannot be selected

here.

Function

Factory setting

Off

Tripping Delay

Factory setting

1 s

Output Relay

Selection (relays)

MR, AL, #1…#5

Factory setting

MR

ATTENTION

!

The phase sequence of the motor supply can be monitored only at the
point of measurement (usually before the contactor). Exchanged leads
between this point and the motor cannot be recognized.

Function

Factory setting

Off

Tripping Delay

Factory setting

2 s

Output Relay

Selection (relays)

MR, AL, #1…#5

Factory setting

MR