5-5 Setting the Operational Parameters

Publication 825-UM001B-EN-P January 2001

Table 5.D Cat. No. 825-M… Operating Parameters (Continued)

➊ If Asymmetry Trip is set to “off”, the programming menu skips to parameter AS Warning.
➋ If AS Warning is set to “off”, the programming menu skips to parameter Overcurr Trip.
➌ If OC Warning is set to “off”, the programming menu skips to parameter Earth Fault Prot.

Group

Required

Option Card

Cat. No.

LCD

Setting

Range

Description

Asymmetry

On/Off ➊

Asymmetry protection
(current measuring
asymmetry) On/Off

5…80

Asymmetry trip
Tripping level in percent

1…25

Asymmetry trip
Tripping delay

All relays

Asymmetry trip
Assignment of relays

On/Off ➋

Asymmetry warning
On/Off

5…80

Asymmetry warning
Warning level in percent

All except

main relay

Asymmetry warning
Assignment of output relay

Overcurrent

On/Off

Overcurrent/locked-rotor
protection On/Off

1.0…6.0

Overcurrent/locked-rotor
Tripping level in …

,

e

0.1…5

Overcurrent/locked-rotor
Tripping delay

All relays

Overcurrent/locked-rotor
Assignment of output relay

On/Off ➌

Overcurrent/locked-rotor
warning On/Off

ASYMMETRY TRIP
ON

AS TRIP LEVEL
35 %

AS TRIP TIME
2.5 sec

ASYMMETRY TRIP
MAIN RELAY

AS WARNING
OFF

AS WARNING LEVEL
20 %

AS WARNING
ALARM RELAY

OVERCURR TRIP
ON

OC TRIP LEVEL
2.4

X

Ie

OC TRIP TIME
0.5 sec

OVERCURRENT TRIP
MAIN RELAY

OC WARNING
OFF