Setting the Operational Parameters 5-4

Publication 825-UM001B-EN-P January 2001

Operating Parameters

Table 5.D Cat. No. 825-M… Operating Parameters

➊ If Primary CT #1 is set to “no”, the programming menu skips to parameter Locked Rot Curr.
➋ If Thermal Warning is set to “off”, the programming menu skips to parameter Asymmetry Trip.

Group

Required

Option Card

Cat. No.

LCD

Setting

Range

Description

Main settings

Mode: Set parameters

0.5…2 000 Rated motor current in A

No/Yes ➊

Use of the primary
transformer

1…2 000

Current ratio of the primary
current transformer e.g.
500 A/5 A, setting = 100
800 A/5 A, setting = 160

2.5…12

Locked rotor and starting
current in …

,

e

1…600

Maximum permissible
locked-rotor time of motor
from cold

Thermal overload

Main

relay/no

relay

Thermal trip, motor
Choice between main
output relay and no relay

On/Off ➋

Thermal warning (motor
temp) On/Off

50…99

Pickup value for thermal
warning temperature rise as
percent of thermal
utilization

All except

main relay

Thermal warning
Assignment of output relay

SET VALUES

FULL LOAD CURR
20 A

PRIMARY C.T. #1
NO

PRIM. C.T. RATIO
1

LOCKED ROT CURR
6 x Ie

LOCKED ROT TIME
10 sec

THERMAL TRIP
MAIN RELAY

THERMAL WARNING
OFF

TH WARNING LEVEL
75 %

TH WARNING
ALARM RELAY