Figure 3.14, Example of 2-phase current sensing, Table 3.o – Rockwell Automation 825 Smart Motor Manager User Manual User Manual

Page 61: Figure 3.14 example of 2-phase current sensing

Advertising
background image

Functions 3-28

Publication 825-UM001B-EN-P January 2001

Table 3.O Earth (Ground) Fault — Holmgreen/Residual Setting Parameters

➊ –5…60

°

C (23…140

°

F)

➋ If auxiliary relays #2 and #3 are assigned to the communication (refer to page

5-16

) they cannot be selected

here.

Earth (Ground) Fault Protection with a Core Balance Current Transformer

This function can be provided by the Cat. No. 825-MST option card.

In isolated, high impedance-earthed or compensated networks, the necessary high sensitivity
is obtained by using a core balance current transformer, whose core surrounds all three of the
phase leads to the motor.
According to the principle of the residual current protection circuit breaker, sensitive
protection against earth (ground) faults is possible. With a low response threshold, quite a
minor insulation fault can lead to a warning or trip at an early stage.

Figure 3.14 Example of 2-Phase Current Sensing

Example of 2-phase current detection and core balance current transformer for sensitive earth (ground) fault protection (3-phase
current detection is also possible)

Trip

Function

Factory setting

On

Response Level

Setting range

10…100%

Factory setting

50%

Setting increments

10%

Tripping Delay

Setting range

0.1…5 s ± 0.4 s

Factory setting

0.5 s

Setting increments

0.1 s

Output Relay

Selection (relays)

MR, AL, #1…#5

Factory setting

MR

825-MCM

P1

P2

S1

S2

L1

L2

P1

P2

S1

S2

L3

3 ~

1

5

3

2

6

4

825-M

M1

S1

S2

·