Rockwell Automation 825 Smart Motor Manager User Manual User Manual
Page 44
Advertising
3-11 Functions
Publication 825-UM001B-EN-P January 2001
2. If no output is assigned the following readout appears:
LCD:
3. Press the Test button.
LCD:
4. After the set trip delay expires, the basic unit must trip.
LCD:
5. The LED lights.
6. The selected output relay picks up.
LCD:
Resetting
Cancel the trip by pressing Reset.
Testing the Warning Functions
Example: Asymmetry warning
1. When in “Set Values” mode, access the selected output relay:
LCD:
ASYMMETRY TRIP
NO OUTPUT RELAY
TEST
AS TRIP TIME
_ _ _sec
ASYMMETRY TRIP
AS WARNING
ALARM RELAY