3-11 Functions

Publication 825-UM001B-EN-P January 2001

2. If no output is assigned the following readout appears:

LCD:

3. Press the Test button.

LCD:

4. After the set trip delay expires, the basic unit must trip.

LCD:

5. The LED lights.

6. The selected output relay picks up.

LCD:

Resetting

Cancel the trip by pressing Reset.

Testing the Warning Functions

Example: Asymmetry warning

1. When in “Set Values” mode, access the selected output relay:

LCD:

ASYMMETRY TRIP
NO OUTPUT RELAY

TEST

AS TRIP TIME
_ _ _sec

ASYMMETRY TRIP

AS WARNING
ALARM RELAY