Warm start, Table 3.s, Monitoring start time setting parameters – Rockwell Automation 825 Smart Motor Manager User Manual User Manual

Page 68

Advertising
background image

3-35 Functions

Publication 825-UM001B-EN-P January 2001

Table 3.S Monitoring Start Time Setting Parameters

➊ –5…60

°

C (23…140

°

F)

➋ If auxiliary relays #2 and #3 are assigned to the communication (refer to page

5-16

) they cannot be selected

here.

Note: With Star-Delta (Wye-Delta) starting, the total starting time (Star and Delta) is
monitored. If immediate switch off is demanded in the event of stalling, monitoring must be
provided by a zero speed switch (function “stalling during starting”).

Note: If the starting current is below 1.2 FLC, then the “Monitoring the Start Time”
function must be activated. After the set max. starting Time has elapsed, the “High
Overload/Stall” function will become active.

Applications:

Slip ring motors

Soft starters

Motor protection with “non-fail-safe mode”, after a control voltage failure

Warm Start

Function

The motor windings may be heated for a short time above the permissible temperature limit.
This applies particularly to rotor-critical motors. The temperature that is permitted for this
short period is approximately 250

°

C and is thus appreciably higher than the continuous

operating temperature of 100…150

°

C. This means that a motor warm from running has a

relatively long permissible starting time. This property of the motor can be used with the
Smart Motor Manager, which is factory-set for one warm start per hour. The tripping time is
then 70% of that from cold. The warm start function is switched off in the factory. As
additional protection for the motor, too many warm starts can be prevented by the “limiting
the number of starts per hour” function.

Function

Factory setting

Off

Max. Starting Time

Setting range

1…240 s ± 0.04 s

Factory setting

10 s ± 0.04 s

Setting increments

1 s

Output Relay

Selection (relays)

MR, AL, #1…#5

Factory setting

MR

Advertising