Figure 3.17, Figure 3.18, Figure 3.19 – Rockwell Automation 825 Smart Motor Manager User Manual User Manual
Page 65: Figure 3.20, Figure 3.20), D figure 3.20

Functions 3-32
Publication 825-UM001B-EN-P January 2001
Figure 3.17 Isolated network: Earth (Ground) Fault on the Leads on the Motor
Side
The basic unit measures the earth current component through C
M
.
Figure 3.18 Network Earthed through a High Impedance: Earth (Ground) Fault on
the Motor Leads
The basic unit measures the vector sum of the earth currents through C
N
and the earthing resistance R.
Compensated network: The basic unit measures the vector sum of the earth currents through C
N
and the compensating coil L.
Figure 3.19 Isolated Network: Earth (Ground) Fault in the Motor
The nearer the fault is to the motor star-point, the smaller the fault current.
Figure 3.20 Network Earthed through a High Impedance: Earth (Ground) Fault on
the Motor
The basic unit measures vector sum of the earth currents through C
N
and the earthing resistance R.
Compensated network: The basic unit measures the vector sum of the earth currents through C
N
and the compensating coil L.
The nearer the fault is to the motor star-point, the smaller the fault current.