Functions 3-32

Publication 825-UM001B-EN-P January 2001

Figure 3.17 Isolated network: Earth (Ground) Fault on the Leads on the Motor
Side

The basic unit measures the earth current component through C

M

.

Figure 3.18 Network Earthed through a High Impedance: Earth (Ground) Fault on
the Motor Leads

The basic unit measures the vector sum of the earth currents through C

N

and the earthing resistance R.

Compensated network: The basic unit measures the vector sum of the earth currents through C

N

and the compensating coil L.

Figure 3.19 Isolated Network: Earth (Ground) Fault in the Motor

The nearer the fault is to the motor star-point, the smaller the fault current.

Figure 3.20 Network Earthed through a High Impedance: Earth (Ground) Fault on
the Motor

The basic unit measures vector sum of the earth currents through C

N

and the earthing resistance R.

Compensated network: The basic unit measures the vector sum of the earth currents through C

N

and the compensating coil L.

The nearer the fault is to the motor star-point, the smaller the fault current.

3 AC

U3

U1

U2

T

1
2

3

K1

825-M

M1

CN

I E

CM

3 AC

U3

U1

U2

T

1
2

3

K1

825-M

M1

CN

I E

CM

R

L

3 AC

T

1

2

3

K1

825-M

M1

CN

I E

CM

U3

U1

U2

3 AC

T

1

2

3

K1

825-M

M1

C

N

I

E

C

M

U

3

U

1

U

2

R

L

Advertising