Figure 3.12, Function of underload protection, Table 3.n – Rockwell Automation 825 Smart Motor Manager User Manual User Manual

Page 59: Underload setting parameters, Figure 3.12 function of underload protection, Table 3.n underload setting parameters

Advertising
background image

Functions 3-26

Publication 825-UM001B-EN-P January 2001

Figure 3.12 Function of Underload Protection

1 Start

,

r

Tripping threshold

2 Nominal operation

t

s

Delayed activation (underload

3 Underload operation

protection not active)

t

A

Starting time

t

v

Tripping delay

,

e

Rated current

t

p

Warning

Table 3.N Underload Setting Parameters

➊ –5…60

°

C (23…140

°

F)

➋ For warning, the set Response Level is the same as the level set for tripping. If the starting current is below

1.2 FLC, then the “Monitoring the Start Time” function must be activated. After the set max. starting Time
has elapsed, the “High Overload/Stall” function will become active.

➌ If auxiliary relays #2 and #3 are assigned to the communication (refer to page

5-16

) they cannot be selected

here.

Warning

Trip

Function

Factory setting

Off

On

Response Level

Setting range

25…100%

,

e

Factory setting

75%

Setting increments

5%

Tripping Delay

Setting range

1…60 s -0.2 s/+0.4 s

Factory setting

10 s

Setting increments

1 s

Delayed Activation of Underload Protection

Setting range

0…240 s +0.4 s/+0.8 s

Factory setting

0 s

Setting increments

1 s

Output Relay

Selection (relays)

AL, #1…#5

MR, AL, #1…#5

Factory setting

AL

MR

t

A

I

1

2

I

e

t

3

3

t

p

t

s

t

v

t

p

I

e

I

I

T