Figure 3.11, Function of high overload and jam protection, Table 3.m – Rockwell Automation 825 Smart Motor Manager User Manual User Manual
Page 57: High overload and jam setting parameters, Application, Table 3.m high overload and jam setting parameters

Functions 3-24
Publication 825-UM001B-EN-P January 2001
Application
•
Conveying systems
•
Mills
•
Mixers
•
Crushers
•
Saws, etc.
Figure 3.11 Function of High Overload and Jam Protection
1
Motor start
,
≥
1.2
,
e
t
V
Tripping delay
2
Nominal operation
4
Jam protection not active
3
High overload or jam
5
Jam protection active (tripping threshold)
Table 3.M High Overload and Jam Setting Parameters
➊ –5…60
°
C (23…140
°
F)
➋ If auxiliary relays #2 and #3 are assigned to the communication (refer to page
) they cannot be selected
here.
Warning ➊
Trip ➊
Function
Factory setting
Off
On
Response Level
Setting range
1…6
,
e
1…6
,
e
Factory setting
2
,
e
2.4
,
e
Setting increments
0.2
,
e
0.2
,
e
Tripping Delay
Setting range
—
0.1…5 s ± 0.04 s
Factory setting
—
0.5 s ± 0.04 s
Setting increments
—
0.1 s
Output Relay ➋
Selection (relays)
AL, #1…#5
MR, AL, #1…#5
Factory setting
AL
MR
t
v
1.1
2.4
1
2
3
I
e
I
4
t
5
≥
1.2