Figure 3.11, Function of high overload and jam protection, Table 3.m – Rockwell Automation 825 Smart Motor Manager User Manual User Manual

Page 57: High overload and jam setting parameters, Application, Table 3.m high overload and jam setting parameters

Advertising
background image

Functions 3-24

Publication 825-UM001B-EN-P January 2001

Application

Conveying systems

Mills

Mixers

Crushers

Saws, etc.

Figure 3.11 Function of High Overload and Jam Protection

1

Motor start

,

1.2

,

e

t

V

Tripping delay

2

Nominal operation

4

Jam protection not active

3

High overload or jam

5

Jam protection active (tripping threshold)

Table 3.M High Overload and Jam Setting Parameters

➊ –5…60

°

C (23…140

°

F)

➋ If auxiliary relays #2 and #3 are assigned to the communication (refer to page

5-16

) they cannot be selected

here.

Warning

Trip

Function

Factory setting

Off

On

Response Level

Setting range

1…6

,

e

1…6

,

e

Factory setting

2

,

e

2.4

,

e

Setting increments

0.2

,

e

0.2

,

e

Tripping Delay

Setting range

0.1…5 s ± 0.04 s

Factory setting

0.5 s ± 0.04 s

Setting increments

0.1 s

Output Relay

Selection (relays)

AL, #1…#5

MR, AL, #1…#5

Factory setting

AL

MR

t

v

1.1

2.4

1

2

3

I

e

I

4

t

5

1.2