Table 3.af, Motor insulation class setting parameters – Rockwell Automation 825 Smart Motor Manager User Manual User Manual

Page 91

Advertising
background image

Functions 3-58

Publication 825-UM001B-EN-P January 2001

This function must be activated so that the coolant temperature may be taken into account in
the thermal image:

Ambient temperature in the thermal image is taken into account.

Insulation class of winding

Table 3.AF Motor Insulation Class Setting Parameters

Limiting winding temperatures of the three insulations classes: E = 120 °C, B = 130 °C, F =
155°C.
When the ambient temperature is taken into consideration, the insulation class needs to be
programmed for correction of the thermal model. Without using PT100 #7 as the ambient
temperature input, the thermal model bases the thermal calculation on an ambient
temperature of 40°C.

Application

With large temperature variation (day/night)

Outdoor installations:

Pumps

Conveyors

Crushers

Saws

Function

Factory setting

Off

Insulation Class

Selection

B, E, F

Factory setting

B

Tamb IN TH IMAGE
ON

MOTOR INSULATION CLASS
B