Figure 3.25, Interruption of a short-circuit, Attention – Rockwell Automation 825 Smart Motor Manager User Manual User Manual
Page 76

3-43 Functions
Publication 825-UM001B-EN-P January 2001
Tripping is delayed by 50 ms. This enables the circuit breaker to be actuated rapidly while
preventing unnecessary tripping by current peaks. In the event of a short-circuit, the separate
output relay #1 trips, regardless of the other protective functions. The output relay #1
actuates a circuit breaker with adequate breaking capacity. To prevent the contactor from
opening under short-circuit conditions, relay MR remains blocked at currents
≥
12 I
e
. If a
thermal trip occurred shortly before the short circuit, relay MR assumes the tripped position
as soon as the current has dropped to < 12 I
e
.
Figure 3.25 Interruption of a Short-Circuit
Application
•
Medium/high-voltage motors
ATTENTION
!
The short-circuit protection function must not be used for switching
off the contactor.
I
t
Q1M
825-M
I
A
II
12
I
e
II
I
e
II
1
2 3
t
v
tt
t
Q
tt
t
LB
tt
Relais #1
t
BL
tt
Relais MR
Q1M Circuit-breaker (tripping relay)
,
Current curve
,
A
Pickup value
,
e
Rated service current
t
v
Tripping delay 50 ms
t
Q
Operating time of the breaker
t
LB
Arc duration
1
Short-circuit
2
Contact separation
3
Short-circuit interruption
t
BL
Relay MR blocked at
≥
12
,
e