Figure 3.25, Interruption of a short-circuit, Attention – Rockwell Automation 825 Smart Motor Manager User Manual User Manual

Page 76

Advertising
background image

3-43 Functions

Publication 825-UM001B-EN-P January 2001

Tripping is delayed by 50 ms. This enables the circuit breaker to be actuated rapidly while
preventing unnecessary tripping by current peaks. In the event of a short-circuit, the separate
output relay #1 trips, regardless of the other protective functions. The output relay #1
actuates a circuit breaker with adequate breaking capacity. To prevent the contactor from
opening under short-circuit conditions, relay MR remains blocked at currents

12 I

e

. If a

thermal trip occurred shortly before the short circuit, relay MR assumes the tripped position
as soon as the current has dropped to < 12 I

e

.

Figure 3.25 Interruption of a Short-Circuit

Application

Medium/high-voltage motors

ATTENTION

!

The short-circuit protection function must not be used for switching
off the contactor.

I

t

Q1M

825-M

I

A

II

12

I

e

II

I

e

II

1

2 3

t

v

tt

t

Q

tt

t

LB

tt

Relais #1

t

BL

tt

Relais MR

Q1M Circuit-breaker (tripping relay)

,

Current curve

,

A

Pickup value

,

e

Rated service current

t

v

Tripping delay 50 ms

t

Q

Operating time of the breaker

t

LB

Arc duration

1

Short-circuit

2

Contact separation

3

Short-circuit interruption

t

BL

Relay MR blocked at

12

,