Star-delta (wye-delta) starting, Figure 3.32, Diagram of star-delta (wye-delta) starting – Rockwell Automation 825 Smart Motor Manager User Manual User Manual

Page 88: Table 3.ac, Star-delta (wye-delta) starting setting parameters

Advertising
background image

3-55 Functions

Publication 825-UM001B-EN-P January 2001

Star-Delta (Wye-Delta) Starting

The Smart Motor Manager issues the command to switch from star to delta (wye to delta) as
soon as the starting current has dropped to the rated value and thus the motor has reached its
normal speed in star (wye). If starting has not been completed within the normal time for this
application [max. star (wye) operation], a change to delta will be made, regardless of the speed
attained.
The permissible time for star (wye) operation can be switched on or off as desired. If it is off,
the change to delta is made solely with reference to the motor current.
If the motor has to be switched off when the normal starting time in star (wye) is exceeded,
the “monitoring starting time” function must also be activated (refer to page

3-34

).

Figure 3.32 Diagram of Star-Delta (Wye-Delta) Starting

Table 3.AC Star-Delta (Wye-Delta) Starting Setting Parameters

Setting

Star (Wye) Relay

Delta Relay

Max. Star (Wye)

Operation

Function

Factory setting

Off

Off

Setting

Setting range

1…240 s

Factory setting

Relay #4

Relay #5

10 s

Setting steps

1 s

Ι

e

80 ms

t

80 ms

I

e

I

Motor

on
off

Motor current

Star operation,
relay #4

Delta operation,
relay #5

Changeover delay