8-8 Error Diagnosis and Troubleshooting

Publication 825-UM001B-EN-P January 2001

Procedure if “ALARM” does not Reset

Indication

LCD: Does not display the type of the alarm (LCD active)

Red LED: Flashing

Cause for this Condition

If the affected alarm function is switched “OFF” before the alarm has disappeared or the
motor has been switched off, then the alarm stays on whether the motor is switched on or
off.

How to Get Rid of Alarm

Go to SET VALUES mode.

Switch on all alarm functions (e.g., “THERMAL WARNING” “ON”).

As soon as the affected alarm function is switched on again, then the alarm condition
will disappear.

Switch alarm function off if not required

Procedure if “TRIP” cannot be Reset

There are two reasons why a trip can not be reset if the motor is not running.

Thermal Trip

Indication

LCD: “THERMAL TRIP”

Red LED: On

How to Reset
The motor must have cooled down to the pre-set level, before the reset is possible:

“TH RESET LEVEL” setting range 10…100%, factory setting 50%.