Applications/Wiring 9-8

Publication 825-UM001B-EN-P January 2001

Two-Speed Motors with Primary Current Transformer

When a primary current transformer is used, two-speed motors of any rating can be
protected.

Primary Circuit

Figure 9.9 Two-Speed Application Utilizing Primary Current Transformer

Separately Ventilated Motors

Because they are cooled constantly, separately ventilated motors exhibit the same thermal
behavior when stationary as when running. Consequently, the cooling ratio must be set to 1.

LCD:

For setting the cooling ratio, refer to

Chapter 5

.

825-MCM

2 (20)

825-M

L1

L2

L3

L1

L2

L3

K2

K1

N
(-)

R

L
(+)

825-MST

Y41

Y42

24 V AC/DC

8 mA

100-M05

100-M05

(I)

(II)

K1

K2

... A / 1 (5) A

(I)

(II)

... A / 1 (5) A

M

3 ~

220...230V AC/DC: R = 27k

/ 5W

110...120V AC/DC: R = 12k

/ 4W

24V AC/DC R = 0

For setting the second rated current (speed II)

refer to

Chapter 5

“Control input #2“

Secondary circuit

COOL-CONST RATIO
1.00