5-13 Setting the Operational Parameters

Publication 825-UM001B-EN-P January 2001

Table 5.D Cat. No. 825-M… Operating Parameters (Continued)

➊ If Phase-Rever Trip is set to “off”, the programming menu skips to parameter Phase Loss Trip.
➋ If Phase Loss Trip is set to “off”, the programming menu skips to parameter PT100 Prot.
➌ If PT100 Prot is set to “off”, the programming menu skips to parameter Output 4…20 mA.

Group

Required

Option Card

Cat. No.

LCD

Setting

Range

Description

Control input #2,
continued

825-MST

Not disabled/

disabled

Underload protection
Active/locked out

Not disabled/

disabled

Limiting starts/hour
Active/locked out

Not disabled/

disabled

PTC protection
Active/locked out

Not disabled/

disabled

PT100 (RTD) protection
Active/locked out

Phase sequence
protection

825-MLV

On/Off ➊

Phase sequence protection
(based on motor supply
voltage)
On/Off

All relays

Phase sequence protection
Assignment of output relay

Phase failure

825-MLV

On/Off ➋

Phase failure
(based on motor supply
voltage) On/Off

All relays

Phase failure
Assignment of output relay

PT 100 (RTD)
temperature sensor

825-MMV

On/Off ➌

PT100 protection
(stator/bearings)
On/Off

On/Off

PT100 #1 protection
On/Off

50…200

PT100 #1
Tripping temperature

On/Off

PT100 #2 protection
On/Off

50…200

PT100 #2
Tripping temperature

UNDERLOAD PROT
NOT DISABLED

START INHIBIT
NOT DISABLED

PTC PROT
NOT DISABLED

PT100 PROT
NOT DISABLED

PHASE-REVER TRIP
OFF

PHASE-REVER TRIP
MAIN RELAY

PHASE LOSS TRIP
OFF

PHASE LOSS TRIP
MAIN RELAY

PT100 PROT
OFF

PT100 #1 TRIP
OFF

#1 TRIP TEMP
50 °C

PT100 #2 TRIP
OFF

#2 TRIP TEMP
50 °C