Reset

When the motor is at standstill, a trip condition can be reset.

Kinds of Reset

Manual reset — Press the reset button on the Bulletin 825 for at least 200 ms

Remote reset — Short circuit terminals Y2l/Y22

Automatic reset — In the mode “set values”, set automatic reset for:

Thermal trip

PTC trip

PT100 trip

Reset Conditions

Thermal — As soon as the temperature rise has dropped to the preset reset
threshold.

PTC detector — As soon as the temperature is below the reset threshold

PT100 detector — As soon as the temperature is below the tripping threshold.

Asymmetry/Phase failure — Manual or remote reset possible

All other trips — Can be reset immediately.

Table 3.V Reset Setting Parameters

Function of the Cat. No. 825-MST Option Card

Short-Circuit

Heavy phase currents caused by short circuits between phases and from phase to earth are
detected by the Cat. No. 825-MST option card. The supply can be interrupted immediately by
controlling the power switching device (e.g., circuit-breaker).
Short-circuit protection is always active. Therefore, the response level must be set somewhat
higher than the maximum starting current.

Setting range

Manual/Automatic

Factory setting

Manual

Reset Threshold of the Thermal Trip

Setting range

10…100%

Factory setting

70%

Setting increments

5%