Chapter 5 Sourcing Current Loop Input Module (1756-IF6CIS) and Isolated Analog Voltage/Current Input Module (1756-IF6I)

1756-IF6CIS – Two-wire transmitter connected to the module and an external,

user-provided power supply providing 24V DC loop power

+

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

VOUT-1

IN-1/I

RTN-1

VOUT-3

IN-3/I

RTN-3

Not used

VOUT-5

IN-5/I

RTN-5

VOUT-0

IN-0/I

RTN-0

VOUT-2

IN-2/I

RTN-2

Not used

VOUT-4

IN-4/I

RTN-4

2-Wire
Transmitter

43471

24V DC

Shield Ground

NOTES:

1. If separate power sources are used, do not exceed the

specified isolation voltage.

2. Do not connect more than two wires to any single terminal.

3. Place additional loop devices (that is, strip chart recorders)

at either ’A’ location in the current loop.

i

A

A