Chapter 4 Non-isolated Analog Voltage/Current Input Modules (1756-IF16, 1756-IF8)
Differential Current
Applications
• Input data for that channel changes to the scaled value
associated with the overrange signal value of the selected
operational range in floating point mode (minimum possible
scaled value) or -32,768 counts in integer mode.
• The ChxUnderrange (x=channel number) tag is set to 1.
In current applications, wire-off detection occurs for one of the
following reasons:
• Because the RTB has been disconnected from the module.
• Both the signal wire and the jumper wire have been
disconnected.
The module reacts with the same conditions as described in
differential voltage applications.
(1)
For more information about tags in the tag editor, see
.
Wire-Off Conditions
When the Wire-Off
condition occurs
These events occur