f. Twist the foil shield and drain wire together to form a single strand.

g. Attach a ground lug and apply heat shrink tubing to the exit area.

2.

Connect the drain wire to a chassis mounting tab.

Use any chassis mounting tab that is designated as a functional signal
ground. The functional earth ground symbol appears near the tab.

3.

When the drain wire is grounded, connect the insulated wires to the
field-side.

45079

45080

Chassis mounting tab

Drain wire with ground lug

4 m or 5 m (#10 or #12)
Star Washer

4 m or 5 m (#10 or #12) Star Washer Phillips
Screw and Star Washer (or SEM Screw)

20918-M

Functional Earth

Ground Symbol