Install ControlLogix I/O Modules Chapter 9
f. Twist the foil shield and drain wire together to form a single strand.
g. Attach a ground lug and apply heat shrink tubing to the exit area.
2.
Connect the drain wire to a chassis mounting tab.
Use any chassis mounting tab that is designated as a functional signal
ground. The functional earth ground symbol appears near the tab.
3.
When the drain wire is grounded, connect the insulated wires to the
field-side.
45079
45080
Chassis mounting tab
Drain wire with ground lug
4 m or 5 m (#10 or #12)
Star Washer
4 m or 5 m (#10 or #12) Star Washer Phillips
Screw and Star Washer (or SEM Screw)
20918-M
Functional Earth
Ground Symbol