Channel status word bits – integer mode – Rockwell Automation 1756-XXXX ControlLogix Analog I/O Modules User Manual

Page 117

Advertising
background image

Publication 1756-UM009C-EN-P - December 2010

117

Sourcing Current Loop Input Module (1756-IF6CIS) and Isolated Analog Voltage/Current Input Module (1756-IF6I) Chapter 5

Channel Status Word Bits – Integer Mode

The Channel Status word has the following differences when used in integer
mode:

• Only Underrange and Overrange conditions are reported by the

module.

• Alarming and Calibration Fault activities are not available, although the

Calibration Fault bit in the Module Fault word will activate if a channel
is not properly calibrated.

• There is only one Channel Status word for all six channels.

When the Calibration Fault bit (bit 7) is set in any of the words, the Calibration
Fault bit (bit 9) is set in the Module Fault word. The table lists the conditions
that set each of the words.

Tag (Status
word)

Bit

Event that sets this tag

ChxUnderrange

Odd-numbered bits from
bit 15…bit 5 (bit 15
represents channel 0).

For a full listing of the
channels these bits
represent,

page 115

.

The underrange bit is set when the input signal at the channel is less than or
equal to the minimum detectable signal.

For more information on the minimum detectable signal for each module, see

page 98

. This bit also sets the appropriate bit in the Channel Fault word.

ChxOverrange

Even-numbered bits from
bit 14…bit 4 (bit 14
represents channel 0).

For a full listing of the
channels these bits
represent,

page 115

.

The overrange bit is set when the input signal at the channel is greater than
or equal to the maximum detectable signal.

For more information on the maximum detectable signal for each module, see

page 98

. This bit also sets the appropriate bit in the Channel Fault word.