Isolated Analog Output Modules (1756-OF6CI and 1756-OF6VI) Chapter 8

1756-OF6CI and 1756-OF6VI
Module Fault and
Status Reporting

The 1756-OF6CI and 1756-OF6VI modules multicast status and fault data to
the owner-listening controller with their channel data. The fault data is
arranged in such a manner as to let you choose the level of granularity for
examining fault conditions.

Three levels of tags work together to provide increasing degree of detail as to
the specific cause of faults on the module.

The table lists tags that can be examined in ladder logic to indicate when a fault
occurs.

Tag

Description

Module Fault
Word

This word provides fault summary reporting. Its tag name is
ModuleFaults.

Channel Fault
Word

This word provides underrange, overrange and communications fault
reporting. Its tag name is ChannelFaults.

Channel Status
Words

This word provides individual channel underrange and overrange fault
reporting for process alarms, rate alarms and calibration faults. Its tag
name is ChxStatus.

IMPORTANT

Differences exist between floating point and integer modes as
they relate to module fault reporting. These differences are
explained in the following two sections.