Publication 1756-UM009C-EN-P - December 2010

189

Install ControlLogix I/O Modules Chapter 9

Connect Wiring

You can use an RTB or a Bulletin 1492 pre-wired Analog Interface Module

(AIFM)

(1)

to connect wiring to your module. If you are using an RTB, follow

the directions in this section to connect wires to the RTB. An AIFM has been
pre-wired before you received it.

If you are using an AIFM to connect wiring to the module, skip this section
and see

page 383

.

Wedge-shaped
keying tab

Module side of the RTB

0

1

2 3

4

5 6

7

20851-M

(1)

The ControlLogix system has been agency certified using only the ControlLogix RTBs (1756-TBCH, 1756-TBNH,
1756-TBSH and 1756-TBS6H). Any application that requires agency certification of the ControlLogix system
using other wiring termination methods may require application specific approval by the certifying agency.

IMPORTANT

For all ControlLogix analog modules, except the 1756-IR6I, we
recommend you use Belden 8761 cable to wire the RTB. For the
1756-IR6I module, we recommend you use Belden 9533 or
83503 cable to wire the RTB.

The RTB terminations can accommodate 22…14 gauge
shielded wire.