Calibrate the ControlLogix Analog I/O Modules Chapter 11
10.
Record the measurement.
11.
Click Next.
A Results wizard displays the status of each channel after calibrating for
a low reference. If channels are OK, continue. If any channel reports an
error, retry steps
7
…
9
until the status is OK.
12.
Click Next.
13.
Set the channels to be calibrated for a high reference.