Communication tab – Rockwell Automation 1756-XXXX ControlLogix Analog I/O Modules User Manual
Page 347

Publication 1756-UM009C-EN-P - December 2010
347
Use Ladder Logic To Perform Run Time Services and Reconfiguration Appendix C
The table contains required output configuration information to perform
output module services. This information is only necessary if you are
configuring the message with RSLogix 5000, versions 9 or earlier:
Communication Tab
The Communication tab provides information on the path of the message
instruction. For example, the slot number of a 1756-IF6I module distinguishes
exactly which module a message is designated for.
Analog Output Modules Configuration Dialog Window Information
Enter the following
To unlatch the
high alarm
To unlatch the
low alarm
To unlatch the
ramp alarm
Service Code
4B
4B
4B
Object Type
0B
0B
0B
Object ID
(Channel Number)
1…6 or 1…8
1…6 or 1…8
1…6 or 1…8
Object Attribute
6F
6E
70
Number of Elements
0 bytes
0 bytes
0 bytes
IMPORTANT
Use the Brown button to see a list of the I/O modules in the
system. You choose a path when you choose a module from
the list.
You must name an I/O module during initial module
configuration to choose a path for your message instruction.
Click OK to set the path.