Chapter 4 Non-isolated Analog Voltage/Current Input Modules (1756-IF16, 1756-IF8)
Choose a Data Format
Data format determines the format of the data returned from the module to
the owner-controller and the features that are available to your application.
You choose a data format when you choose a
.
When you choose a Communication Format, you can select one of two data
formats:
• Integer mode
• Floating point mode
The table shows features that are available in each format.
Data Format
Features Available
Features Not Available
Integer mode
Multiple input ranges
Module filter
Real time sampling
Process alarms
Digital filtering
Rate alarms
Scaling
Floating point mode
All features
See below
IMPORTANT
When using the 1756-IF16 module in single-ended mode (that
is, 16-channel mode) with a floating point data format, process
alarms and rate alarms are not available.
This condition exists when the 1756-IF16 is only wired for
single-ended mode. The 1756-IF8 is not affected.