Analog I/O Module Specifications Appendix A

1756-OF8

ControlLogix voltage/current output analog module

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

Shield Ground

i

Current
Output
Load

1756-OF8 Current

VOUT-4

IOUT-4

RTN

VOUT-5

VOUT-6

IOUT-6

RTN

VOUT-7

IOUT-5

IOUT-7

VOUT-0

IOUT-0

RTN

VOUT-1

VOUT-2

IOUT-2

RTN

VOUT-3

IOUT-1

IOUT-3

A

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

+

Shield Ground

1756-OF8 Voltage

VOUT-4

IOUT-4

RTN

VOUT-5

VOUT-6

IOUT-6

RTN

VOUT-7

IOUT-5

IOUT-7

VOUT-0

IOUT-0

RTN

VOUT-1

VOUT-2

IOUT-2

RTN

VOUT-3

IOUT-1

IOUT-3

· Place additional loop devices (such as strip chart recorders) at

the A location noted above.

· Do not connect more than two wires to any single terminal.
· All terminals marked RTN are connected internally.

· Do not connect more than two wires to any single terminal.
· All terminals marked RTN are connected internally.

Input Signal to User Count Conversion - 1756-OF8

Range

Low Signal and User Counts

High Signal and User Counts

0...20 mA

0 mA

-32768 counts

21.2916 mA

32767 counts

±10V

-10.4336V

-32768 counts

10.4336V

32767 counts

Technical Specifications - 1756-OF8

Attribute

1756-OF8

Outputs

8 voltage or current

Output range

± 10.4V
0…21 mA

Resolution

15 bits across 21 mA - 650 nA/bit
15 bits across 10.4V - 320

μ

V/bit

Current draw @ 5.1V

150 mA

ANALOG OUTPUT