Non-isolated Analog Output Modules (1756-OF4 and 1756-OF8) Chapter 7

1756-OF4 and 1756-OF8
Fault Reporting in
Integer Mode

The illustration provides an overview of the fault reporting process in
integer mode.

15

14

13

12

11

5

4

3

2

1

0

15 = AnalogGroupFault
12 = Calibrating
11 = Cal Fault
14 and 13 are not used by
1756-OF4 or 1756-OF8

7 = Ch7Fault
6 = Ch6fault
5 = Ch5Fault
4 = Ch4Fault

Output in Hold conditions
(even numbered bits) must
be monitored here.

5

4

9

8

7

6

15

14

13

12

11

10

15 = Ch0OpenWire
14 = Ch0InHold
13 = Ch1OpenWire
12 = Ch1InHold
11 = Ch2OpenWire
10 = Ch2InHold
9 = Ch3OpenWire
8 = Ch3InHold

IMPORTANT: Bits 0…7 not used on 1756-OF4

If set, any bit in the Channel Fault word, also sets
the Analog Group Fault in the Module Fault word.

When the module is calibrating, all
bits in the Channel Fault word are set.

7

6

3

2

1

0

7 = Ch4OpenWire
6 = Ch4InHold
5 = Ch5OpenWire
4 = Ch5InHold
3 = Ch6OpenWire
2 = Ch6InHold
1 = Ch7OpenWire
0 = Ch7InHold

Open Wire conditions
(odd numbered bits) set
the appropriate bits in the
Channel fault Word.

Module Fault Word

(described on

page 164

)

Channel Fault Word

(described on

page 164

)

Channel Status Words

(described on

page 165

)

3 = Ch3Fault
2 = Ch2Fault
1 = Ch1Fault
0 = Ch0Fault