Rockwell Automation 1756-XXXX ControlLogix Analog I/O Modules User Manual

Page 54

Advertising
background image

54

Publication 1756-UM009C-EN-P - December 2010

Chapter 3 ControlLogix Analog I/O Module Features

Difference Between Integer and Floating Point

The key difference between choosing integer mode or floating point mode is
that the integer is fixed between -32,768…32,767 counts and floating point
mode provides scaling to represent I/O data in specific engineering units for
your application. Module resolution remains constant between the formats at
0.34 µA/count.

For example, the table shows the difference in the data returned from the
1756-IF6I module to the controller between data formats. In this case, the
module uses the 0 mA…20 mA input range with 0 mA scaled to 0%
and 20 mA scaled to 100%, as shown on page 50.

1756-IF6I Module using different data types

Signal Value

Fixed Number of Counts
in Integer Mode

Data Representation in Floating
Point Mode (Engineering Units)

0 mA

-32768 counts

-25%

4 mA

-20341 counts

0%

12 mA

4514 counts

50%

20 mA

29369 counts

100%

21.09376 mA

32767 counts

106.25%

Advertising