Calibrate the ControlLogix Analog I/O Modules Chapter 11

A Results wizard displays the status of each channel after calibrating for
a high reference. If channels are OK, continue. If any channels report an
error, retry

step 7

until the status is OK.

After you have completed both low and high reference calibration, this
window shows the status of both.

9.

Click Finish.