Limits Tab

The Limits tab lets you program clamping and ramp limitations that may
prevent damage to equipment.

1.

Choose from the options on the Limits tab.

Field Name

Description

Channel

Click the channel that is being
configured.

Limits

High Clamp
Low Clamp

Type a high and low clamp value that
limits the output from the analog
module within this range.

See

page 152

and

page 170

for details.

See Important on

page 224

.

Ramp in Run Mode

Check the box to enable ramping in Run
mode.

Ramp Rate

Entry field is enabled if the Ramp in Run
Mode box is checked. Type a value that
sets the maximum ramp rate for a
module in Run mode.

See

page 169

in

Chapter 8

for details.

Disable All Alarms

Check the box to disable all alarms.

Important: When you disable all
alarms, you disable process, rate, and
channel diagnostic alarms (for example,
underrange and overrange).
We recommend that you disable only
unused channels so extraneous alarm
bits are not set.