Rockwell Automation 1756-XXXX ControlLogix Analog I/O Modules User Manual

Page 242

Advertising
background image

242

Publication 1756-UM009C-EN-P - December 2010

Chapter 11 Calibrate the ControlLogix Analog I/O Modules

While you are online, you must access the Module Properties dialog box.
See

page 207

in

Chapter 10

for procedures.

Follow these steps to calibrate your module.

1.

Connect your voltage calibrator to the module.

2.

Go to the Configuration tab on the Module Properties dialog box.

3.

At the Input Range, choose the range from the pull-down menu to
calibrate the channels.

4.

Click OK.

IMPORTANT

The following examples show how you calibrate the
1756-IF6I module for voltage. Calibrating the modules for
current uses the same process as calibrating the 1756-IF6I
module for voltage except the change in input signal.

Advertising