Chapter 11 Calibrate the ControlLogix Analog I/O Modules
While you are online, you must access the Module Properties dialog box.
See
in
for procedures.
Follow these steps to calibrate your module.
1.
Connect your voltage calibrator to the module.
2.
Go to the Configuration tab on the Module Properties dialog box.
3.
At the Input Range, choose the range from the pull-down menu to
calibrate the channels.
4.
Click OK.
IMPORTANT
The following examples show how you calibrate the
1756-IF6I module for voltage. Calibrating the modules for
current uses the same process as calibrating the 1756-IF6I
module for voltage except the change in input signal.