Real time sampling underrange/overrange detection, Real time sampling, Underrange/overrange detection – Rockwell Automation 1756-XXXX ControlLogix Analog I/O Modules User Manual

Page 98

Advertising
background image

98

Publication 1756-UM009C-EN-P - December 2010

Chapter 5 Sourcing Current Loop Input Module (1756-IF6CIS) and Isolated Analog Voltage/Current Input Module (1756-IF6I)

Real Time Sampling

This parameter instructs the module to scan its input channels and obtain all
available data. After the channels are scanned, the module multicasts that data.

During module configuration, you specify a real time sampling (RTS) period
and a requested packet interval (RPI) period. These features both instruct the
module to multicast data, but only the RTS feature instructs the module to
scan its channels before multicasting.

For more information on real time sampling, see

page 24

. For an example of

how to set the RTS rate, see

page 210

.

Underrange/Overrange Detection

This alarm feature detects when the isolated input module is operating beyond
limits set by the input range. For example, if you are using the 1756-IF6I
module in the 0…10V input range and the module voltage increases to 11V,
the overrange detects this condition.

The table lists the input ranges of the 1756-IF6CIS and 1756-IF6I modules
and the lowest/highest signal available in each range before the module detects
an underrange/overrange condition.

Input Module

Range

Lowest Signal
in Range

Highest Signal
in Range

1756-IF6CIS

0 mA…20 mA

0 mA

21.09376 mA

1756-IF6I

+/- 10V

0V…10V

0V…5V

0 mA…20 mA

-10.54688V

0V

0V

0 mA

10.54688V

10.54688V

5.27344V

21.09376 mA

IMPORTANT

Be careful when ‘disabling all alarms’ on the channel because it
also disables the underrange/overrange detection feature. If
alarms are disabled, overrange/underrange is zero and the only
way you can discover a wire-off detection is from the input
value itself. If you need to detect a wire-off status, do not
‘disable all alarms’.

We recommend that you disable only unused channels so
extraneous alarm bits are not set.

Advertising