Chapter 11 Calibrate the ControlLogix Analog I/O Modules
The Output Reference Signals wizard appears to show which channels
will be calibrated for a low reference and the range of the calibration. It
also shows what reference signal is expected at the input.
9.
Click Next.
10.
Record the results of your measurement.
TIP
Click Back to return to the last window to make any
necessary changes. Click Stop to halt the calibration
process, if necessary.