344

Publication 1756-UM009C-EN-P - December 2010

Appendix C Use Ladder Logic To Perform Run Time Services and Reconfiguration

Enter Message Configuration

After creating a tag, you must enter certain parameters for the message
configuration. This information is entered on the Configuration and
Communication tabs of the Message Configuration dialog box.

The Message Configuration dialog box is accessed by clicking the box with the
ellipses (in the Message Control field).

IMPORTANT

In RSLogix 5000 software, version 10 and later, the Message
Configuration dialog boxes changed significantly to make it
easier for you to configure your messages.

• For example, in version 9 and earlier, depending on the

Message Type, you are required to configure some
combination of the following:

Service Code

Object Type

Object ID

Object Attribute

Source

Number of Elements

Destination

• In version 10 and later, after you choose a Service Type,

RSLogix 5000 software fills in most of the fields listed
above. The fields you must fill in are dependent on what
Service Type you choose. For example, with the High Alarm
Unlatch, you must know only the Source Element and the
Destination.

A table describes the relationship of the fields in both dialog
boxes on

page 345

.